IBM的服务器感叹号亮黄灯 无法启动系统

时间:2022-05-30 14:51:00|栏目:IDC机房|点击:

各位专家,我这里有一个IBM X3850 X5的服务器,感叹号亮黄灯,光路诊断卡上LOG,FAN亮黄灯,怎么回事呢? 重新启动到这儿就启动不了..

服务器灯显示

FAN 代表风扇,楼主可以在通电状态下,把机箱盖打开,看看里面哪个风扇旁边亮黄灯就是哪个风扇有故障了,也可以连接服务器后面管理口(IMM),登录进去看看日志,基本就能知道问题所在了;

服务器异常

我查看了,
结果如下:
10. E -- -- 9/5/2016:6:32:5 -- N -- 0x800b050a1e81ffff -- Non-redundant:Insufficient Resources for "Cooling Zone 1" has asserted

11. E -- -- 9/5/2016:6:31:35 -- N -- 0x800b010a1e82ffff -- Redundancy Lost for "Cooling Zone 2" has asserted

12. E -- -- 9/5/2016:6:31:26 -- N -- 0x800b010a1e81ffff -- Redundancy Lost for "Cooling Zone 1" has asserted

处理方式如下:

1. I -- -- 9/14/2016:2:56:19 -- N -- 0x4000000e00000000 -- Remote Login Successful. Login ID: USERID from Web at IP address 192.168.70.77

2. I -- -- 9/14/2016:2:46:54 -- N -- 0x800301081381ffff -- Sensor "AC RESTORE" has asserted

3. E -- -- 9/14/2016:2:46:54 -- N -- 0x800b01081381ffff -- Redundancy Lost for "Power Group 1" has asserted

4. I -- -- 9/14/2016:2:46:48 -- N -- 0x806f00091381ffff -- "Host Power" has been turned off

5. I -- -- 9/14/2016:2:46:34 -- N -- 0x4000001700000000 -- ENET[sp-ethernetport] IP-Cfg:HstName=IMM-6CAE8B78ACA9, IP@= 192.168.70.125 ,NetMsk=255.255.255.0, GW@ =0.0.0.0

6. I -- -- 9/14/2016:2:46:34 -- N -- 0x4000001900000000 -- LAN: Ethernet[eth1] interface is now active

7. I -- -- 9/14/2016:2:46:13 -- N -- 0x806f00091381ffff -- "Host Power" has been turned off

8. E -- -- 9/14/2016:2:46:13 -- N -- 0x800b050a1e81ffff -- Non-redundant:Insufficient Resources for "Cooling Zone 1" has asserted

9. I -- -- 9/5/2016:6:32:5 -- N -- 0x806f00091381ffff -- "Host Power" has been turned off

10. E -- -- 9/5/2016:6:32:5 -- N -- 0x800b050a1e81ffff -- Non-redundant:Insufficient Resources for "Cooling Zone 1" has asserted

11. E -- -- 9/5/2016:6:31:35 -- N -- 0x800b010a1e82ffff -- Redundancy Lost for "Cooling Zone 2" has asserted

12. E -- -- 9/5/2016:6:31:26 -- N -- 0x800b010a1e81ffff -- Redundancy Lost for "Cooling Zone 1" has asserted

13. I -- -- 9/5/2016:6:31:17 -- N -- 0x800800041d01ffff -- Device "Fan 1" has been removed from unit "Chassis 1"

14. I -- -- 9/5/2016:6:31:10 -- N -- 0x800800041d02ffff -- Device "Fan 2" has been removed from unit "Chassis 1"

15. I -- -- 9/5/2016:6:30:58 -- N -- 0x800800041d04ffff -- Device "Fan 4" has been removed from unit "Chassis 1"

16. E -- -- 9/5/2016:6:30:57 -- C -- 0x800102041d010002 -- Numeric sensor "Fan1 Tach" going low (lower critical) has asserted

17. E -- -- 9/5/2016:6:30:51 -- C -- 0x800102041d020002 -- Numeric sensor "Fan2 Tach" going low (lower critical) has asserted

18. I -- -- 9/5/2016:6:30:32 -- N -- 0x816f00091381ffff -- "Host Power" has been turned on

上一篇:公司OA系统服务器被卡死的原因是软件引起(已处理)

栏    目:IDC机房

下一篇:IDRAC8 Express和IDRAC8 Enterprise功能上有什么不同

本文标题: IBM的服务器感叹号亮黄灯 无法启动系统

本文地址:https://idc91.com/idc/4464.html

广告投放 | 联系我们 | 免责申明

重要申明:本站所有的文章、图片、评论等,均由网友发表或上传并维护或收集自网络,属个人行为,与本站立场无关。

如果侵犯了您的权利,请与我们联系,我们将在24小时内进行处理、任何非本站因素导致的法律后果,本站均不负任何责任。

Copyright © 2023 IDC91.COM 版权所有晋ICP备17006296号